1207   properties "unique" for names

Created: 23 Jan 2014

Status: Not Applicable

Part: Part 6 (2009-12; Edition 2)

Links:

Page: 61

Clause: 9.3.2

Paragraph:

Category: No impact on this part

Issue

In the restriction for the IED name is written.
*) The IED name shall be unique within the SCL file

For me it is not clear what is meaning of "unique"?
The IED-Names "IED1" and "IED2" are different, that ist clear, but are the same name written in different letter (upper case vs. lower case) also different?

for example: The first IED has the name "IED1" the second IED inside the substation has the name "ied1". Is this allowed? The names are different !

Proposal

Please clear this item !

Discussion Created Status
31 Jan 14 Not Applicable
xs:Name (type of IED name) is case sensitive - therefore ied1 and IED1 are different, and I agree with Christian thus allowed.
30 Jan 14 Triage
IED1 and ied1 are different and are thus allowed.
However this is very bad practice and should be avoided.
23 Jan 14 Triage

 