1180   Equivalent command to CFG-2

Created: 22 Oct 2013

Status: Not Applicable

Part: Part 90-5 (2013; Edition 1, Synchrophasor)

Links:

Page: 57

Clause: 9.2.1

Paragraph: Table 1

Category: Issue for edition 2 of this part

Issue

Table 1 defines the equivalent of IEEE C37.118 CFG-2 to be "Read actual measurements from data model (MMXU, etc.)".
CFG-2 indicates measurements currently being reported (transmitted) in
the data frame.
Thus, the correct 90-5 mapping would be a GetDataSetDirectory of the data set being used.

Proposal

Correct table as mentioned above.

Note: for CFG-1 the exact mapping would be to the directory services (LD, LN, etc.).

Discussion Created Status
Approve 11 Oct 22 Not Applicable
90-5 has been deprecated and replaced by IEC 62351-6 , IEC 62351-9, and IEC 61850-8-1 Edition 2 Amd 1 28 Feb 22 Approval (N/A)

 