1126   Several control data objects to be changed to settings

Created: 22 May 2013

Status: In Force (green)

Part: Part 7-420 (2008; DER)

Links:

Page: 49, 57, 89

Clause: 6.2.3, 7.1.3, 8.5.5

Paragraph:

Category: Issue for edition 2 of this part

Issue

As an outcome of other Tissues (see e.g. 899, 904 and 1101) it should be carefully checked if all control data objects (DOs) in all IEC 61850-7-420 LNs are really controls or rather settings.

Proposal

- Change data type (CDC) of DOs DCIP.TrgSpd and DCIP.EngTrqSet from APC to ASG
- Change CDC of DOs ExtGain, PhLdComp, StabSigWash, StabGain, ExtCeilV and ExtCeilA of LN DEXT from APC to ASG
- Change CDC of DOs DEXC.ExtVTms and DEXC.ExtVDurTms from INC to ING
- Change CDC of DO MFLW.FanSpdSet from APC to ASG
[Decided by WG 17 IEC 61850-7-420 UML Task Force]

Discussion Created Status
The logical node MFLW has been moved to IEC 61850-7-4 Ed. 2.1 - see Tissue 1215 03 Mar 14 In Force (green)
30 Jan 14 In Force (green)