1055 EntryTime never used in 9-2Created: 22 Mar 2013 Status: In Force (green) Part: Part 9-2 (2011; Edition 2) Links: Page: 24, Clause: 8,6, Paragraph: Category: Issue for edition 2 of this part Issue "EntryTime" (48 bit time representation in ASN.1 with an epoch of 1984) is used exclusively for log entries, never in 9-2. It could confuse users since the timestamps are transmitted as TimeStamp (64 bits, epoch of 1970). Proposal Remove EntryTime reference in Table 15